Environmental specifications
Table: Appliance compute node environmental specifications
Specification | 5372 Appliance compute node |
|---|---|
Operating temperature | ASHRAE A2 (10°C to 35°C ) (50°F to 95°F) |
Non-operating temperature | -40 °C to 70 °C (-40 °F to 158 °F) The non-operating temperature is defined as the temperature of the system when the system is turned off. It is also referred to as the storage temperature. Cohesity recommends that you do not store the system in an environment where the temperatures fall outside of the listed temperature range. |
Operating humidity (RH) | 8% RH to 85% RH non-condensing |
Non-operating humidity | 8% RH to 90% RH non-condensing |
Operating altitude (feet) | 3050 m (10,006 ft) |
Temperature gradient (per hour) | 10°C/h (50°F/h) |
Table: Cohesity 5U84 Primary Storage Shelf / 5U84 Expansion Storage Shelf environmental specifications
Specification | Description |
|---|---|
Temperature range | Operating: 5º to 35ºC (de-rate 5ºC above 2,133m (7,000')) (41°F to 95°F) Non-operating: -40°C to 70°C (-40°F to 158°f) |
Relative humidity | Operating: 20%rh to 80%rh non-condensing Non-operating: 5%rh to 100%rh non-condensing |
Operating altitude | -30 to 3048m ( -100 to 10000ft) De-rate 5°C above 2134m (7000ft) |
Non-operating altitude | -305 to 12192m ( -1000 to 40000ft) |
Maximum wet bulb | Operating: 28°C Non-operating: 29°C |
See 5U84 Storage Shelf technical specifications.
See Protocol standards.